Conductor table from NBS Circular 31, a public-domain NIST publication
Every voltage drop calculator uses K = 12.9 for copper and none of them say why. It is not a code secret. It is 10.37, which is what the National Bureau of Standards measured for a circular mil of copper a foot long, multiplied by 1.216 because the conductor is at 75 degrees rather than 20, and by another 1.02 because a stranded wire is laid in a helix and is longer than the cable it sits in. Every step of that is checkable in a public-domain government pamphlet, and this page shows the working.
Voltage drop on a run
A
ft
%
Voltage drop only. This never makes a conductor smaller than its ampacity requires, and ampacity is not calculated here. See the section below.
Specification summary
Generated from on .
Reopen that address to reproduce these figures exactly.
Entered
Result
Voltage along the run, against your limit
Worked example
A 20 A branch circuit at 120 V, single phase, running 100 ft one way in #12 copper, checked against a 3% limit.
K. 12.87 ohm-cmil per foot, derived below rather than looked up.
The formula. 2 × 12.87 × 20 × 100 = 51,480, divided by the 6,530 circular mils of a #12.
The drop.7.88 V, which on 120 V is 6.57%.
At the load. 112.12 V arrives instead of 120.
What passes. 3% of 120 V is 3.6 V, so you need 51,480 / 3.6 = 14,300 circular mils. A #10 is 10,380 and still fails at 4.13%. The first size that passes is #8, at 2.60%.
Two gauge sizes, not one, and that surprises people every time. It follows from the gage law: three gauge numbers doubles the copper and halves the drop, so one size only buys you about 21%. If the run is 60% over the limit, one size up will not save it. The other lever is linear: halve the distance and you halve the drop.
The formula
One line, and the only part anybody argues about is K:
Vd = f × K × I × L / CM
f
2 for single phase, because the current goes out and comes back. 1.732 for three phase
K
ohm-circular mils per foot. 12.87 for copper and 21.1 for aluminium at 75 C, derived below
I
load current, amps
L
ONE-WAY run length, ft. The factor f already accounts for the return
CM
conductor area in circular mils, from the NBS table
The commonest mistake here is doubling the length as well as using the factor of 2, which reports twice the real drop. The factor is the round trip. Measure the run one way.
Why this page exists at all
There are hundreds of voltage drop calculators. They all use the same formula and the same constant, and between them they cite almost nothing. K = 12.9 gets attributed to a table in a code book that is behind a login, and there the trail stops.
It turns out the trail does not need to stop there. The National Bureau of Standards published Copper Wire Tables as Circular 31, it is a US government document in the public domain, NIST hosts the PDF, and it contains everything: the law that defines the wire gauge, the diameter and circular mils of every size, and the resistance per thousand feet of standard annealed copper at 20 degrees.
From those three things K falls out in two steps, both of them physics rather than convention. That is the whole page: a constant everyone uses and nobody explains, explained, with a link to a document you can read for free.
The two things that could not be sourced that way are said plainly where they appear. The status of the 3% figure is asserted from secondary sources and labelled. The ampacity table is not here at all.
NBS Circular 31 Table 5, checked against the gage law
AWG
Diameter, mils
5 x 92^((36-n)/39)
Circular mils
Derived, mils²
Ohms per 1,000 ft at 20 C
K = R x CM / 1000
4/0
460.0
460.0
211,600
211,600
0.04901
10.37
3/0
409.6
409.6
167,800
167,806
0.06182
10.37
2/0
364.8
364.8
133,100
133,077
0.07793
10.37
1/0
324.9
324.9
105,600
105,535
0.09825
10.38
1
289.3
289.3
83,690
83,693
0.1239
10.37
2
257.6
257.6
66,360
66,371
0.1563
10.37
3
229.4
229.4
52,620
52,635
0.1971
10.37
4
204.3
204.3
41,740
41,741
0.2485
10.37
6
162.0
162.0
26,240
26,251
0.3952
10.37
8
128.5
128.5
16,510
16,510
0.6281
10.37
10
101.9
101.9
10,380
10,383
0.9988
10.37
12
80.8
80.8
6,530
6,530
1.59
10.38
14
64.1
64.1
4,110
4,107
2.52
10.36
Read 2026-09-08. Columns two, four and six are as the circular prints them. Columns three and five are this page applying the gage law, and the last is K worked out from the row itself.
The wire gauge is a formula, and a government document says so
American Wire Gauge looks like an arbitrary list of sizes that runs backwards. It is not a list at all. The National Bureau of Standards sets it out as a law:
The gage is formed by the specification of two diameters and the law that a given number of intermediate diameters are formed by geometrical progression. Thus, the diameter of No. 0000 is defined as 0.4600 inch and of No. 36 as 0.0050 inch. There are 38 sizes between these two, hence the ratio of any diameter to the diameter of the next larger gage number = 1.122 932 2.
Two fixed ends, 0.4600 in at No. 0000 and 0.0050 in at No. 36, and everything between them in geometric progression. That ratio, 1.1229322, is 92 to the power of one thirty-ninth, so the diameter of any gauge is:
d (mils) = 5 × 92(36 − n)/39
Run it and every published circular-mil figure falls out. A #10 comes to 101.9 mils, so 10,383 circular mils, against the 10,380 the circular prints. The table below does that check on all thirteen sizes.
Two consequences the circular states outright, and they are exact rather than rules of thumb:
Three gauge numbers doubles the area. The ratio cubed is 1.4160, and squared that is 2.0050. So a #7 has twice the copper of a #10, and half the resistance.
Six gauge numbers doubles the diameter. The sixth power of the ratio is 2.0050, which the circular gives as 2.0050. So six sizes up is four times the area and a quarter of the resistance.
Which is worth carrying around. If a #10 is dropping 6 volts and you need 3, you need three gauge numbers, not one.
Where 12.9 comes from, in three steps you can check
Every voltage drop calculator uses K = 12.9 for copper and 21.2 for aluminium. Almost none of them say what K is or where it came from, and the usual gesture is at a code book behind a login.
K is simply the resistance of one circular mil of conductor, one foot long. So it is the published resistance per 1,000 ft times the circular mils, divided by 1,000, and you can compute it from the NBS table on any row:
K20 = 0.9988 × 10,380 / 1,000 = 10.37 (that is the #10 row)
Do it on all thirteen rows and it lands on 10.37 every time, because that is what resistivity means: it is a property of the copper, not of the wire size. The last column of the table below is that calculation.
So why does the industry say 12.9? Two adjustments, both physical:
Temperature. The NBS figures are at 20 °C. The industry constant is quoted at 75 °C, a conductor working hard. The circular's own temperature coefficient for annealed copper is 0.00393 per degree, so 55 degrees multiplies resistance by 1.216: 10.37 × 1.216 = 12.61.
Stranding. A stranded conductor's wires are laid in a helix, so each wire is about 2% longer than the cable it is in, and carries about 2% more resistance. 12.61 × 1.02 = 12.87.
Which is 12.9. And aluminium of the standard grade is defined as 61% the conductivity of copper, so its K is 12.87 / 0.61 = 21.1, which is the 21.2 everybody quotes.
None of that is a secret and none of it needs a code book. It needed a sixty-year-old government pamphlet and a calculator.
One-way length, and the mistake that doubles your answer
The factor of 2 in the single-phase formula is the round trip: current leaves on one conductor and returns on the other, and both of them have resistance.
So the length you enter is the one-way distance, panel to load. Entering the round trip and keeping the factor of 2 reports twice the real drop, and it is the single commonest error on this calculation. It usually shows up as somebody concluding they need 4/0 for a garage circuit.
Three phase uses 1.732, the square root of three, because the return path in a balanced three-phase circuit is shared between the phases rather than doubled.
Why one size up so often is not enough
The gage law makes this predictable. Consecutive gauge numbers differ in area by a factor of about 1.26, so going up one size cuts the drop by about 21%. Three sizes doubles the area and halves the drop.
That means a run failing at 6.6% against a 3% limit is not one size short. It needs the area roughly doubled, so three gauge numbers, or the next size that clears the circular-mil figure the calculator prints.
The other lever is length, and it is linear rather than logarithmic. Halving the run halves the drop exactly. On a long outbuilding feed it is often cheaper to move the subpanel than to upsize the whole run.
Raising the voltage is the third and it is quadratic in effect: the same power at 240 V draws half the current of 120 V, and half the current on twice the voltage is a quarter of the percentage drop.
Temperature, and why K is quoted hot
Copper's resistance rises with temperature, at 0.00393 per degree by the NBS figure. A conductor working near its rating sits far above room temperature, and the industry constant is quoted at 75 °C for that reason: it is the pessimistic case, and voltage drop should be checked at the condition that makes it worst.
The difference is not small. Between 20 and 75 degrees the resistance is up by nearly 22%, which is most of the gap between the 10.37 in the government table and the 12.9 everyone uses.
If your conductor genuinely runs cool, the real drop will be lower than this page reports, and being wrong in that direction is the right way round.
The 3% figure is a recommendation, not a rule
Nearly every voltage drop calculator presents 3% on a branch circuit and 5% overall as a code limit. In the NEC as published they sit in Informational Notes, at 210.19 for branch circuits and 215.2 for feeders, and NEC 90.5 defines informational notes as explanatory material that is not enforceable as a requirement.
This page could not verify that against the primary document, for the same reason the ampacity table is missing: NFPA's reader cannot be read from here. It is stated on the strength of secondary sources and it is flagged as such rather than presented as established. If it matters to your job, read the code itself or ask your inspector.
What is not in dispute is the practical part. Some jurisdictions adopt the 3% and 5% figures as mandatory local amendments, which is exactly the pattern this site keeps finding in the IRC: a model document says one thing and the place you are actually building says another. So the calculator lets you set the limit rather than assuming one, and defaults to 3% because that is the figure people are usually working to.
And whether or not it is enforceable, it is good engineering. A 3% drop on a 120 V circuit is 3.6 V, and equipment is designed for a supply within a band.
What this page will not do, and why that matters more than usual
This page does not size a conductor for ampacity, and you must not use it that way.
Two different questions get asked of a wire. Will the voltage at the far end be high enough for the equipment to work properly? That is voltage drop, it is the arithmetic on this page, and getting it wrong makes a motor run hot or a light dim.
Will the wire itself get hot enough to be a fire? That is ampacity. It comes from NEC Table 310.16, adjusted for ambient temperature, for the number of current-carrying conductors bundled together, and for the temperature rating of the terminations at both ends. Getting it wrong burns a house down.
That table is not on this page because it could not be obtained from a source worth trusting. NFPA's free-access reader is a JavaScript application behind a login and returns nothing to a fetch; every reproduction found sat on a commercial site or a document-sharing service. This site does not launder a safety table by copying it from a stranger, and a conductor's ampacity is the last figure on earth to guess at.
So: size for ampacity first, from the code, then check voltage drop here and go up if it fails. That is the order the two questions come in anyway. Voltage drop only ever makes a conductor bigger, never smaller.
The one document behind this page
Read 2026-09-08. Copper Wire Tables, NBS Circular 31, 4th edition, United States Department of Commerce, National Bureau of Standards. Table 5 gives diameter, circular mils and ohms per 1,000 ft at 20 C for standard annealed copper. A US government publication in the public domain, hosted by NIST. Every figure on this page is either from it or derived from it.
It is worth saying why a single source is enough here, when most pages on this site carry several. Everything on this page is either printed in that circular or derived from what is printed in it by arithmetic you can repeat. There is nothing to triangulate: the AWG ratio is a definition, the resistance table is a measurement published by the national metrology institute, and K is the two of them multiplied together.
The claims this page could not source that way are labelled where they appear: the status of the 3% figure, and the ampacity table that is absent altogether.
Frequently asked questions
What is the formula for voltage drop?
For single phase, Vd = 2 x K x I x L / CM, where K is 12.87 for copper at 75 C, I is the current in amps, L is the ONE-WAY run length in feet and CM is the conductor area in circular mils. For three phase the 2 becomes 1.732. The factor already accounts for the return conductor, so do not double the length as well.
Where does the 12.9 constant come from?
From the resistivity of copper. The National Bureau of Standards published the resistance of standard annealed copper at 20 C, and multiplying any row's ohms per 1,000 ft by its circular mils gives 10.37 every time. Multiply that by 1.216 for a conductor at 75 C rather than 20, using the NBS temperature coefficient of 0.00393, and by about 1.02 for the helical lay of stranding, and you get 12.87.
Is 3% voltage drop a code requirement?
In the NEC as published the 3% branch-circuit and 5% total figures sit in Informational Notes, and NEC 90.5 makes informational notes non-enforceable. This page could not verify that against the primary document, which is behind a login, so treat it as reported rather than established. Some jurisdictions adopt the figures as mandatory local amendments, so ask your inspector.
How much voltage drop on 100 feet of 12 gauge wire?
At 20 A on 120 V single phase, 7.88 V, which is 6.57%. That is more than double a 3% target. You would need about 14,300 circular mils to come in under 3%, so #8 copper: #10 still fails at 4.13%.
Do I use one-way or round-trip length?
One way. The factor of 2 in the single-phase formula is the round trip already. Entering the round-trip distance as well reports twice the real drop, and it is the commonest mistake on this calculation.
How much worse is aluminium than copper?
About 64% more drop at the same size. Standard grade aluminium conductor is defined as 61% the conductivity of copper, so its K is 12.87 divided by 0.61, which is 21.1. Termination compatibility and torque are separate questions this page does not cover.
Does voltage drop affect what size wire I need?
It can only make it bigger, never smaller. Size the conductor for ampacity first, from the code, then check the voltage drop and go up if it fails. Ampacity is a fire-safety question and it is not calculated on this page.
Check these numbers yourself
Copper Wire Tables, NBS Circular 31, 4th editionUnited States Department of Commerce, National Bureau of Standards. Table 5 gives diameter, circular mils and ohms per 1,000 ft at 20 C for standard annealed copper. A US government publication in the public domain, hosted by NIST. Every figure on this page is either from it or derived from it.
How every figure here is verified: Sources & Method. Who builds this: About. Found something wrong? Tell us and it gets fixed or removed.
Figures on this page last checked against the source documents on 2026-09-08. Codes are amended locally; confirm against the edition your jurisdiction enforces.
Voltage drop only. This page does not size anything for ampacity. Conductor ampacity comes from NEC Table 310.16 with adjustments for ambient temperature, conductor bundling and termination ratings, that table could not be obtained from a trustworthy source, and it is not reproduced here. Size for ampacity from the code first and use this to check performance. The wire table was read from NBS Circular 31 on 8 September 2026.