IRC R316 barriers, and 16 CFR 460.13 at 3 1/2 inches
Foam is sold by the board foot, one square foot at one inch thick, and every price quoted per square foot is that number times a thickness. You can prove it from a published price table: the figures at two and three inches are the one inch figures multiplied out, to the cent. Which means the headline of one to four dollars fifty per square foot, printed with no thickness attached, cannot be applied to anything.
Board feet, R-value and the barrier the code wants
ft
ft
sq ft
in
R/in
R
%
The R per inch is an input because it belongs to a product, not to a foam type. Both open and closed cell cover a wide range and 16 CFR 460.13 already requires every foamed-in-place product to publish its R-value at 3 1/2 inches.
Specification summary
Generated from on .
Reopen that address to reproduce these figures exactly.
Entered
Result
Cost per square foot is a straight line through zero
Worked example
A 40 by 25 ft attic roofline, open cell at 5 1/2 in, R-3.7 per inch from the product's data sheet, 10% yield allowance.
Area. 40 × 25 = 1,000 sq ft.
Board feet. 1,000 × 5.5 = 5,500, because a board foot is a square foot at an inch.
With yield.6,050 board feet.
R achieved. 3.7 × 5.5 = R-20.4.
Cost. At $0.44 to $1.50 per board foot, $2,662 to $9,075.
Covering. Attic, so an ignition barrier: one of 8 named materials.
Now switch the foam to closed cell without touching anything else. The same 6,050 board feet costs $7,563 to $17,545, which is nearly three times as much, and it is not the same insulation: closed cell has a much higher R per inch, so nobody would apply it at 5 1/2 inches to reach R-20. That is the trap in comparing foams at a fixed thickness or a fixed price per square foot, and it is why the honest comparison is at a fixed R-value in board feet.
The formula
One multiplication for the quantity, and the unit is the whole point:
board feet = A × t R = r × t $/sq ft = $/board foot × t
A
area in square feet
t
thickness in inches
board foot
one square foot at one inch. The unit foam is sold in
r
R per inch, from the product data sheet, not from this page
3 1/2 in
the thickness 16 CFR 460.13 makes every foam publish an R-value at
The third equation is the one people skip. A price per square foot is not a property of a foam, it is a property of a foam at a thickness, and a table of them at 1, 2 and 3 inches is one number printed three times. Quote in board feet and the arithmetic stops being ambiguous.
How you can tell a price table is really per board foot
This page reads a published cost guide rather than a manufacturer document, because the code does not price anything and no data sheet does either. What it adds to the guide is an observation the guide does not make about itself.
The table gives cost per square foot for open and closed cell at 1, 2 and 3 inches. Multiply the one inch row by the thickness and you reproduce the other two rows: open cell 0.88 and 3.00 at two inches, 1.32 and 4.50 at three against a printed 1.30 and 4.50. Closed cell lands exactly at both.
So the table has one row of data in it. The underlying figures are 0.44 to 1.50 per board foot for open cell and 1.25 to 2.90 for closed, and everything else on it is arithmetic.
That matters because the same publisher's headline figure, one dollar to four dollars fifty per square foot, appears elsewhere with no thickness attached. It is one of those rows with the unit removed, and there is no way to tell which.
A published per square foot table, and its own one inch row
Thickness
Open cell, as printed
Closed cell, as printed
Open cell, 1 in row × thickness
Closed cell, 1 in row × thickness
1 in
$0.44 to $1.50
$1.25 to $2.90
$0.44 to $1.50
$1.25 to $2.90
2 in
$0.88 to $3.00
$2.50 to $5.80
$0.88 to $3.00
$2.50 to $5.80
3 in
$1.30 to $4.50
$3.75 to $8.70
$1.32 to $4.50
$3.75 to $8.70
Read 2026-09-10. The first two price columns are quoted from This Old House, how much does spray foam insulation cost, written by Stephanie Minasian-Koncewicz, updated 13 April 2026. The last two are this page multiplying its one inch row by the thickness.
A price per square foot with no thickness on it means nothing
Foam is sold by the board foot, which is one square foot at one inch thick. That is the unit an installer buys in, prices in and pumps in, and every figure quoted per square foot is that number multiplied by a thickness.
You do not have to take that on trust. Here is a published price table that gives cost per square foot at three thicknesses, with the one inch row multiplied out beside it:
This Old House, how much does spray foam insulation cost, written by Stephanie Minasian-Koncewicz, updated 13 April 2026, against its own one inch row
Thickness
Open cell, as printed
Closed cell, as printed
Open cell, 1 in row × thickness
Closed cell, 1 in row × thickness
1 in
$0.44 to $1.50
$1.25 to $2.90
$0.44 to $1.50
$1.25 to $2.90
2 in
$0.88 to $3.00
$2.50 to $5.80
$0.88 to $3.00
$2.50 to $5.80
3 in
$1.30 to $4.50
$3.75 to $8.70
$1.32 to $4.50
$3.75 to $8.70
The last two columns are not from the source. They are the first two predicted from its one inch row, and they land on it to the cent at 2 inches and within two cents at 3.
So the table has one row of data in it. Open cell is $0.44 to $1.50 per board foot and closed cell is $1.25 to $2.90, and every other figure on that table is one of those times the inches.
Which is why a headline of "$1.00 to $4.50 per square foot", which appears on the same page with no thickness attached, cannot be applied to a job. It is a board foot price with the unit removed, and you cannot get it back without knowing how deep the foam went.
Ask for a quote in board feet. Any foam contractor works in them, the number is checkable against the rig's own output, and it is the only form in which two quotes for different thicknesses can be compared.
You are not allowed to leave it exposed
Foam plastic is combustible and the code treats it as such. The default requirement is not a recommendation:
Unless otherwise allowed in Section R316.5, foam plastic shall be separated from the interior of a building by an approved thermal barrier of not less than 1/2-inch (12.7 mm) gypsum wallboard, 23/32-inch (18.2 mm) wood structural panel or a material that is tested in accordance with and meets the acceptance criteria of both the Temperature Transmission Fire Test and the Integrity Fire Test of NFPA 275.
Half inch gypsum, 23/32 wood structural panel, or a material tested to NFPA 275. That is the thermal barrier, and it applies to foam anywhere it faces the interior of the building.
Attics and crawl spaces get relief from it, on conditions:
The thermal barrier specified in Section R316.4 is not required where all of the following apply: 1. Attic access is required by Section R807.1. 2. The space is entered only for purposes of repairs or maintenance. 3. The foam plastic insulation has been tested in accordance with Section R316.6 or the foam plastic insulation is protected against ignition using one of the following ignition barrier materials.
So in an unfinished attic you may use an ignition barrier instead, and the code names which ones. R316.5.3, attics:
1-1/2-inch-thick (38 mm) mineral fiber insulation
1/4-inch-thick (6.4 mm) wood structural panels
3/8-inch (9.5 mm) particleboard
1/4-inch (6.4 mm) hardboard
3/8-inch (9.5 mm) gypsum board
Corrosion-resistant steel having a base metal thickness of 0.016 inch (0.406 mm)
1-1/2-inch-thick (38 mm) cellulose insulation
1/4-inch (6.4 mm) fiber-cement panel, soffit or backer board
R316.5.4, crawl spaces:
1-1/2-inch-thick (38 mm) mineral fiber insulation
1/4-inch-thick (6.4 mm) wood structural panels
3/8-inch (9.5 mm) particleboard
1/4-inch (6.4 mm) hardboard
3/8-inch (9.5 mm) gypsum board
Corrosion-resistant steel having a base metal thickness of 0.016 inch (0.406 mm)
1/4-inch (6.4 mm) fiber-cement panel, soffit or backer board
Count them. The attic list has 8 entries and the crawl space list has 7. The one that appears in the first and not the second is:
1-1/2-inch-thick (38 mm) cellulose insulation
Adjacent subsections of the same section, otherwise word for word identical, one option dropped and no reason given. Worth knowing before you specify the same detail in both spaces.
Both lists have an escape. Neither barrier is required where the foam has been tested in accordance with R316.6, which is how the intumescent coatings sold for exactly this purpose work. That testing belongs to a specific product and its evaluation report, not to foam in general.
Open cell against closed cell, which are two materials with one name
They are sprayed with the same rig by the same crew and they behave nothing alike.
Closed cell is denser and has a much higher R per inch, so it reaches a given R-value in fewer inches. That matters where depth is limited, which is most retrofits: a 2x4 rafter bay is 3 1/2 inches and no amount of open cell will make it perform like a 2x6.
Closed cell also resists vapour and open cell does not. At sufficient thickness closed cell is a vapour retarder in its own right, which changes where the assembly can dry to. That is an assembly design decision rather than a quantity, and getting it wrong traps water in a roof deck.
Open cell is cheaper per board foot and much cheaper per inch. The published figures on this page put it at roughly a third of closed cell for the same board feet, which is why it is normal in an open attic roofline where depth is free.
The calculator prices both at your board feet so you can see the difference, and says on the row that they are not the same R-value, because comparing them at a fixed thickness is the mistake this whole page is about.
What the rig meters, and why yield is an input
Foam arrives as two liquids in two drums and becomes insulation on the wall. That has consequences no bagged product has.
Yield is theoretical. A set of drums has a nominal board foot yield, and it is achieved at the right temperature, the right pressure and the right ratio. Cold drums, a long hose or a worn mixing chamber all cost yield, and the material that comes out off-ratio is not insulation, it is waste that still has to be trimmed off.
Trim is real on any framed cavity. Foam is sprayed proud and cut back flush so drywall can go on, and what comes off the face is gone. On an open roofline there is no trimming and the allowance should drop.
The default here is 10%, it is this page's own figure and it is an input, for the same reason the compaction allowance on the gravel page is. No data sheet publishes one.
And it is why an installed quote is usually the sane way to buy foam. The material, the rig, the operator and the yield risk all sit on the contractor's side of the line, which is not true of a bag of cellulose.
And it has to pass a flame spread test before any of that
The barrier requirements sit on top of a materials requirement that applies to the foam itself:
Unless otherwise allowed in Section R316.5, foam plastic, or foam plastic cores used as a component in manufactured assemblies, used in building construction shall have a flame spread index of not more than 75 and shall have a smoke-developed index of not more than 450 when tested in the maximum thickness and density intended for use in accordance with ASTM E84 or UL 723.
Flame spread index not more than 75, smoke-developed index not more than 450, tested in the maximum thickness and density intended for use. That last clause is the one to read twice: a foam that passes at two inches has not been shown to pass at six, and the thickness tested is a property of the product's evaluation report.
For comparison, ordinary wall and ceiling finishes are allowed a flame spread index of 200. Foam is held to 75, which is well under half of it.
None of this is a quantity question, which is why no other spray foam calculator mentions it. It is also the part of a foam job that gets failed at inspection, and the barrier is not something you can add afterwards without pulling the foam about.
Comparing two foams, and the one thickness the FTC picked
Open cell and closed cell are different materials sold under one name. They differ in R per inch, in density, in what they do to water vapour and in what they cost per board foot, and the difference in R per inch is roughly a factor of two.
Which makes any comparison at a fixed price per square foot meaningless, and any comparison at a fixed R-value a comparison of two different thicknesses. The Federal Trade Commission solved this by fixing the thickness:
For foamed-in-place insulations, you must show the R-value of your product at 3 1/2 inches. You can also show R-values at other thicknesses.
3.5 inches. Every foamed-in-place product sold to homeowners has to publish its R-value at that one depth, so two fact sheets can be read side by side without arithmetic.
This page will not print an R per inch for either type. It is a property of a specific product, it appears on that product's data sheet and in its evaluation report, and the range across products within one type is wide enough that an average would mislead. The calculator asks for yours, the same way the blown-in page asks for your bag's coverage chart.
The one figure worth carrying between them: the price table above gives a single R-value column covering both open and closed cell, which cannot be right for two materials that differ by a factor of two. Read R-values off the product, not off a cost guide.
The sources
Read 2026-09-10.
Seattle Residential Code, Chapter 3, Section R316 Foam Plastic, City of Seattle, adopting the 2018 International Residential Code, Sections R316.3, R316.4, R316.5.3 and R316.5.4. Requires foam plastic to be separated from the interior by an approved thermal barrier, and lists the ignition barrier materials that substitute for it in an attic and in a crawl space. The two lists differ by one entry.
16 CFR 460.13, What must be on the fact sheet, Federal Trade Commission, section 460.13(c)(1). Requires foamed-in-place insulation to show its R-value at 3 1/2 inches, which is the one thickness at which two foams can be compared without doing arithmetic on somebody's marketing.
Seattle is used because codes.iccsafe.org returns HTTP 403 and cannot be fetched, and because a city that publishes its adopted code as a PDF states its edition and jurisdiction on the document. Your jurisdiction may amend R316, and several do. Check the edition your building department enforces.
The price table is quoted with its byline and date and is one publisher's national figures. This site publishes no price of its own. What this page adds to it is the observation that it is a board foot table, which its publisher does not say.
Frequently asked questions
What is a board foot of spray foam?
One square foot at one inch thick. It is the unit foam is sold, quoted and metered in, so 1,000 square feet sprayed to 5 1/2 inches is 5,500 board feet. Any price quoted per square foot is a board foot price times a thickness, and without the thickness it cannot be applied to a job.
How much does spray foam cost per square foot?
That question has no answer without a thickness. A published guide gives open cell at $0.44 to $1.50 per board foot and closed cell at $1.25 to $2.90, so a square foot at three inches is three times either. Its own headline of $1.00 to $4.50 per square foot is one of those figures with the thickness removed.
How thick should spray foam be?
Thick enough to reach the R-value your climate zone and code edition require, which is a separate question answered on the R-value calculator here. Divide that target by your product's R per inch. Then check the product's evaluation report covers that thickness, because IRC R316.3 requires the flame spread test to be run at the maximum thickness intended for use.
Does spray foam need to be covered?
Yes. IRC R316.4 requires foam plastic to be separated from the interior of a building by an approved thermal barrier: 1/2 inch gypsum wallboard, 23/32 inch wood structural panel, or a material tested to NFPA 275. Attics and crawl spaces may substitute an ignition barrier under R316.5.3 and R316.5.4, and both sections list the materials that qualify.
What is an ignition barrier?
A lighter covering the code accepts in an attic or crawl space in place of a full thermal barrier. R316.5.3 names eight materials for attics, including 1 1/2 inch mineral fibre, 1/4 inch wood structural panels, 3/8 inch gypsum board and 1 1/2 inch cellulose. Neither barrier is required where the foam itself has been tested under R316.6, which is what the intumescent coatings sold for this purpose are for.
Are the attic and crawl space barrier lists the same?
Almost, and not quite. The attic list in R316.5.3 has eight materials and the crawl space list in R316.5.4 has seven. The one in the first and not the second is 1 1/2 inch thick cellulose insulation. Adjacent subsections, otherwise word for word identical, one option dropped.
What R-value is spray foam per inch?
It depends on the product, and this page will not print a figure for either type because the range within a type is wide. Read it off the data sheet. 16 CFR 460.13 requires every foamed-in-place insulation to publish its R-value at 3 1/2 inches, which is the one depth at which two products can be compared without arithmetic.
Is open cell or closed cell better?
They are different materials for different jobs. Closed cell reaches a given R-value in fewer inches and resists vapour; open cell is roughly a third of the cost for the same board feet and lets the assembly dry. Depth available and where the assembly needs to dry to decide it, not price per square foot.
Check these numbers yourself
Seattle Residential Code, Chapter 3, Section R316 Foam PlasticCity of Seattle, adopting the 2018 International Residential Code, sections R316.3, R316.4, R316.5.3 and R316.5.4, read 2026-09-10. Requires foam plastic to be separated from the interior by an approved thermal barrier, sets a flame spread index limit of 75 tested at the maximum thickness intended for use, and lists the ignition barrier materials that substitute for the thermal barrier in an attic and in a crawl space. The two lists differ by exactly one entry. Seattle is used because codes.iccsafe.org returns HTTP 403.
16 CFR 460.13, What must be on the fact sheetFederal Trade Commission, section 460.13(c)(1), read 2026-09-10. Requires foamed-in-place insulation to show its R-value at 3 1/2 inches, which is the one thickness at which two foam products can be compared directly.
This Old House, how much does spray foam insulation costWritten by Stephanie Minasian-Koncewicz, updated 13 April 2026, read 2026-09-10. Publishes cost per square foot for open and closed cell at 1, 2 and 3 inches. Every row is the one inch row times the thickness, which is how this page derives the per board foot figures it uses. The publisher does not describe its own table that way.
How every figure here is verified: Sources & Method. Who builds this: About. Found something wrong? Tell us and it gets fixed or removed.
Figures on this page last checked against the source documents on 2026-09-10. Codes are amended locally; confirm against the edition your jurisdiction enforces.
The R per inch is not published here for either foam type, because it belongs to a specific product rather than to a category, and 16 CFR 460.13 already requires every foamed-in-place product to publish its own at 3 1/2 inches. The per board foot figures are this page reading a published thickness table, quoted with its byline and date; this site publishes no price of its own. The yield allowance is this page's own figure and is an input. IRC R316 is quoted from the Seattle Residential Code as read on 10 September 2026 and your jurisdiction may amend it. Whether an assembly can dry, and in which direction, is a design question this page does not answer.