Home › Concrete › Concrete Footing Calculator
Concrete Footing Calculator
Pier and column pads sized the way R403.1.1 sizes them
Halve the soil bearing under a pier and the pad does not double. It grows by about 41 percent on a side, because the code sizes it by area and area is a square. Everybody expects the wrong answer here, in both directions.
Pier and column footing
Sized the way IRC R403.1.1 sizes a pier or column footing: tributary load divided by the allowable soil pressure from Table R401.4.1. Deck footings are a different table and are on the deck footing calculator.
Specification summary
Generated from on . Reopen that address to reproduce these figures exactly.
Entered
Result
Worked example
- The load is the area times the load on it. 144 sq ft at 50 psf is 7,200 lb. Tributary area is half the span to the next support in each direction, which for a post in the middle of a 12 by 12 bay is the whole 144.
- The area is the load divided by the bearing. 7,200 / 1,500 = 4.80 sq ft, which is a 26.3 in square pad.
- Now double the soil bearing to 3,000 psf. The area halves to 2.40 sq ft, and the pad goes to 18.6 in. Not 13.2. The side moved by a factor of 0.71, which is one over the square root of two.
- The projection is what sets the thickness. A 26.3 in pad under an 8 in pier projects 9.15 in each side, and R403.1.1 says the projection shall not exceed the thickness. So that pad needs to be at least 10 in thick, not the 6 in minimum.
- Push the load to 24,000 lb and the rule bites hard. That needs 16 sq ft, a 48 in pad, projecting 20 in. On an 8 in pad the projection is two and a half times the thickness, and the pad is cantilevering further than it can carry.
The formula
- P
- the load reaching this footing, including the pad and the soil on it
- q
- the allowable soil bearing pressure from Table R401.4.1, not a guess
- √A
- why the side moves with the square root and not with the load
- T
- the pad thickness, which R403.1.1 requires to be at least the projection
Why this is a different page from the foundation calculator
Prices for ready-mix and bagged concrete
Tributary area, and the half-span rule
What the pad weighs, and why that is not a rounding error
What this page does not decide
Frequently asked questions
- How do I size a concrete footing for a post?
- Divide the load the post carries by the allowable soil bearing pressure. That gives the area in square feet, and the side of a square pad is the square root of it. A post carrying 7,200 lb on 1,500 psf soil needs 4.8 sq ft, which is a 26.3 in square pad. Then check the thickness against the projection.
- Does doubling the load double the footing?
- No, and this is the one people get wrong. It doubles the AREA, so it multiplies the side by the square root of two, about 1.41. A pad for twice the load is 41% wider, not twice as wide. The same applies going the other way when the soil is better.
- How thick does a pier footing need to be?
- At least as thick as it projects past the column, per R403.1.1: the projection shall not exceed the thickness of the footing. A 26 in pad under an 8 in pier projects 9 in, so it needs to be 9 in thick or more, not the 6 in that is the code minimum elsewhere. Sizing the area and then pouring the minimum thickness is the commonest error on this calculation.
- What is tributary area for a post?
- The floor area that drains to it: half the span to the next support in every direction. A post in the middle of a bay with 12 ft spans both ways carries a 12 by 12 square, 144 sq ft. A post at the end of a run carries about half that, because there is nothing on the far side.
- Is a deck footing sized the same way?
- It can be, but the prescriptive route is different. AWC DCA 6 Table 4 sizes deck footings directly from the beam and joist spans at an assumed 1,500 psf soil, and that is the table an inspector will be holding. The deck footing calculator on this site reads it.
- Should I include the weight of the footing itself?
- Yes, and most calculators do not. Concrete is about 150 lb per cubic foot, so a 48 in pad 20 in thick is roughly 4,000 lb standing on the same soil as the load above it. On small pads it does not matter. Over about a 36 in pad it does.
- Can I use a round footing instead of a square one?
- Yes, and the area is what matters, so a round pad of the same area does the same job. The diameter for a given area is about 1.13 times the side of the equivalent square. Round is what you get from an auger, square is what you get from a form, and the choice is usually made by the tool rather than the code.
Check these numbers yourself
- 2018 Seattle Residential Code, Chapter 4 FoundationsSeattle Department of Construction and Inspections. Read 2026-09-09. Source of Section R403.1.1, which sizes pier and column footings from the tributary load and the allowable soil pressure and sets the 2 in minimum and thickness-maximum on the projection, and of Table R401.4.1.
How every figure here is verified: Sources & Method. Who builds this: About. Found something wrong? Tell us and it gets fixed or removed.
Figures on this page last checked against the source documents on 2026-09-09. Codes are amended locally; confirm against the edition your jurisdiction enforces.
Related calculators
- Foundation Calculator the continuous wall footing
- Deck Footing Calculator AWC DCA 6 Table 4
- Load Calculator where the load came from
- Retaining Wall Calculator IRC R404.4, both thresholds, quoted
- Concrete Calculator volume, bags and a truck
- Rebar Calculator if the pad needs steel
- Brick Calculator Joint and tie requirements quoted from IRC R606.3.1 and R606.13.2
- Concrete Block Calculator Nominal module from CMHA CMU-TEC-001-23
- Concrete Driveway Calculator The garage floor row of Table R402.2 is the honest benchmark
- Concrete Finish Calculator Published finish rates
This sizes the bearing area and checks the projection. It does not design the footing. A pad whose projection approaches its thickness is bending, and reinforcement, punching shear and eccentric loading are all outside the IRC's prescriptive rules and outside this page. The load per square foot is your figure and it is the input that matters most. Depth below grade is set by a local frost table. Soil below 1,500 psf requires an investigation rather than a calculation.