Nails & Numbers

How to Install Fiber Cement Siding

Fiber cement goes on a wall that has already been half built. The barrier behind it, the flashing around the openings and the wind exposure of the site are all settled before the first plank is lifted, and each of them is governed by a section of the code with a number. The plank itself is governed by the manufacturer. Getting those two authorities the right way round is most of the job.

The wall gets a barrier before it gets a board

Nothing goes on the sheathing until the water-resistive barrier is on it, and the section that requires it contains two different lap dimensions in two short sentences:

One layer of No. 15 asphalt felt, free from holes and breaks, complying with ASTM D226 for Type 1 felt or other approved water-resistive barrier shall be applied over studs or sheathing of all exterior walls. No.15 asphalt felt shall be applied horizontally, with the upper layer lapped over the lower layer not less than 2 inches (51 mm). Where joints occur, felt shall be lapped not less than 6 inches (152 mm).

The 2018 IRC wording of R703.2, as printed on page 439 of Seattle's 2018 residential code

Two inches where a course laps the one below. Six inches where one roll ends and the next begins. Both are minimums and both mean a roll covers less wall than its label says.

The other three phrases are the ones that get skipped. One layer, so doubling up is not the requirement and does not substitute for lapping correctly. Free from holes and breaks, which a barrier torn off its staples in a wind is not. All exterior walls, including the short return behind a porch roof that nobody can see and water can reach.

Housewraps fall under the other approved barriers the section allows, and the same IRC text sends those to the barrier manufacturer's installation instructions. The 2 in and 6 in are the code floor for felt, not a specification for your wrap.

Check your jurisdiction on this one. The Seattle code prints that IRC paragraph inside double parentheses and follows it with a replacement section tagged [W], which requires not fewer than one layer of barrier and lists four compliance routes, No. 15 felt to ASTM D226 Type 1 among them, without stating either lap dimension.

How much barrier a wall actually takes, once the lap is counted

Because a 36 in roll only delivers 34 in per course after the 2 in lap, the barrier never divides evenly into a wall height, and the last partial row has to be a full row of material. The result is not a smooth percentage. It steps.

Our arithmetic on the 2 in course lap in R703.2, for a 36 in wide roll run horizontally. Sheet bought is per linear foot of wall
Wall heightRows of 36 in sheetSheet bought per ft of wallWall covered per ftOver the wall area by
8 ft39 ft8 ft12.5%
9 ft412 ft9 ft33.3%
10 ft412 ft10 ft20.0%
16 ft618 ft16 ft12.5%
18 ft721 ft18 ft16.7%
20 ft824 ft20 ft20.0%

A nine foot wall is the worst case in that table by a wide margin. It needs a fourth row for its last six inches, and it finishes 33 percent over the wall area while an eight foot wall on the same roll finishes 12.5 percent over. One foot of extra wall height costs an extra row on every elevation of the building.

This is a per-wall figure. The strip trimmed off the top row is reusable elsewhere only where it is still wide enough to lap properly, which on a tall gable it often is and on a run of short walls it often is not. Ordering every elevation at the 12.5 percent an eight foot wall produces is how a barrier order runs short on a house with taller walls. The siding calculator counts the rows from the roll dimensions you actually bought.

Then the flashing, which no quantity can rescue

The barrier is a plane. The flashing is what keeps that plane continuous where things poke through it:

Approved corrosion-resistant flashing shall be applied shingle-fashion in a manner to prevent entry of water into the wall cavity or penetration of water to the building structural framing components. ... The flashing shall extend to the surface of the exterior wall finish.

R703.4, page 444 of the same Seattle document, which tags the section [W]. The ellipsis stands for two omitted sentences on the AAMA standards for membrane flashings

Shingle-fashion is the whole instruction. Every piece laps over the piece below it, in the direction water travels, so that water arriving on the outside of the assembly stays on the outside. A head flashing tucked under the barrier instead of over it, or a sill pan lapped the wrong way, does not leak slowly. It collects.

The failure happens behind the barrier line, so nothing about it shows on the face of the cladding. A wall can be wetting and drying behind a perfectly straight course line for years, which is why this is checked at each opening as the wall goes up rather than at the end.

Exposure decides the order, and it is not yours to choose

Lap siding covers the wall at its exposure and is invoiced at its face width, so you always buy more board than you have wall. On fiber cement the code sets a floor and the product sets the rest. R703.10.2, as printed in the same Seattle document, requires fiber cement lap siding to be lapped a minimum of 1 1/4 in and to be installed in accordance with the manufacturer's instructions. So the exposure you work to is the one printed for the plank you bought, and it can never leave less than 1 1/4 in of lap.

That makes the exposure the one figure to pin down before any order goes in, since every quantity below is a multiple of it:

Our arithmetic for 1,500 sq ft of net wall, using face and exposure pairs from this site's siding and fiber cement calculators. Each pair leaves a 1 1/4 in lap, the R703.10.2 minimum; they are worked examples, not any manufacturer's published figures
Board faceExposureBoard per sq ft of wallLinear feet of boardBoard area boughtBought and lapped out of sight
12 in10 3/4 in1.1161,674 ft1,674 sq ft174 sq ft
10 in8 3/4 in1.1432,057 ft1,714 sq ft214 sq ft
8 1/4 in7 in1.1792,571 ft1,768 sq ft268 sq ft
8 in6 3/4 in1.1852,667 ft1,778 sq ft278 sq ft

Read the last column rather than the first. On the same 1,500 sq ft wall the narrowest board buries 278 sq ft of material behind the course above and the widest buries 174. That 104 sq ft difference is not waste, and no waste allowance covers it. It is the lap doing its job, permanently out of sight.

Now compare the two boards near 8 in. Both leave the same 1 1/4 in lap, yet the 8 in board at 6 3/4 in needs about 95 more linear feet on this wall than the 8 1/4 in board at 7 in, and 10 sq ft more board. Linear footage depends only on the exposure; the face width changes what you pay for, not how many feet you order.

That is the column to order from. Fiber cement lap is bought by the linear foot, and until you know the exposure the square footage of your wall tells you nothing about how much to buy. The fiber cement siding calculator runs it from your own elevations.

Check the wind table before you plan any fastening

Table R703.3(1) gives the prescriptive fastening schedule for wall coverings. Table R703.3.2 decides whether you are allowed to use it:

Table R703.3.2, maximum mean roof height for attachment per Table R703.3(1)
Ultimate design wind speedExposure BExposure CExposure D
115 mphNot limited50 ft20 ft
120 mphNot limited30 ftDesign required
130 mph60 ft15 ftDesign required
140 mph35 ftDesign requiredDesign required

Table R703.3.2 on page 443 of the 2018 Seattle Residential Code

Four of those twelve cells have no prescriptive answer at all. At 140 mph in Exposure C or D, at 130 in D, and at 120 in D, the attachment has to be engineered against component and cladding loads, and no table and no calculator can give you a fastening schedule.

The height table is also not the only trigger. R703.3.2 cuts in wherever the design wind pressure exceeds 30 psf, whatever the height column says, and it directs that the loads be determined using an effective wind area of 10 square feet.

Exposure here is about the ground around the house, not the weather it gets. In the IRC definitions of R301.2.1.4, which Chapter 3 of the Seattle code prints inside double parentheses ahead of its own, B covers urban, suburban and wooded areas; C is open terrain with scattered obstructions; D is flat, unobstructed ground with wind coming over open water, mud flats, salt flats or unbroken ice. The section assigns a category for each wind direction considered, so one house can sit in two columns, and that column decides whether any of this is a lookup.

The fastener figures everyone quotes are the vinyl ones

This is the error worth carrying away from the page, because it is repeated on a lot of siding advice and it is a category mistake rather than a rounding one.

IRC Chapter 7 contains a very specific and very quotable set of fastener requirements. A 0.120 inch shank diameter nail with a 0.313 inch head, or a 16 gage staple with a 3/8 to 1/2 inch crown. Fasteners penetrating a minimum of 1 1/4 inches into framing, sheathing or other nailable substrate, and extending a minimum of 1/4 inch beyond the opposite face where they go fully through.

Every one of those numbers sits in Section R703.11, which is titled vinyl siding. They are the prescriptive requirements for vinyl, they open with the words unless specified otherwise by the manufacturer's instructions, and they are not the fiber cement schedule. The same section requires vinyl to be certified and labeled as conforming to ASTM D3679, a vinyl product standard with nothing to say about fiber cement.

Fiber cement has its own rows in Table R703.3(1): a minimum nominal thickness of 5/16 in for both panel and lap siding, and 6d common nails, 2 in by 0.113 in, into studs through wood structural panel sheathing, with a 6d common or an 11 gage roofing nail listed for lap siding fixed direct to studs. R703.10 then lets panel siding be fastened to that table or to the approved manufacturer's instructions, and requires lap siding to be installed in accordance with the manufacturer's instructions. A 1 1/4 inch penetration figure lifted off the vinyl section is a figure nobody wrote for fiber cement.

There is a cheerful version of this mistake and a serious one. The cheerful one is quoting the wrong fastener on a forum. The serious one is buying fasteners for a whole house against it.

How long fiber cement siding lasts, and what the sources actually say

How long it lasts is the most asked question about the material, and the documents read for this page answer it poorly. IRC Chapter 7 is a construction standard and sets no service life for any cladding. This Old House's cost guide lists a 50 year life with proper installation among its pros and says some companies offer a 30-year warranty, but it does not say what the 50 years rests on.

So this page does not print a lifespan as a finding. What the code does govern is the work the cladding depends on, and it is not the board:

The practical consequence: read the installation instructions and the warranty before the delivery arrives rather than after.

The order of work, and what it costs

The sequence follows from the sections above rather than from preference.

  1. Establish the wind exposure and the mean roof height, and check Table R703.3.2. If the answer is Design required, the fastening is an engineering question and everything downstream waits on it.
  2. Get the exposure from the installation instructions for the product you have actually bought, confirm it leaves at least the 1 1/4 in lap R703.10.2 sets, and order the linear feet from it.
  3. Barrier over studs or sheathing, all walls, 2 in course laps and 6 in at joints for felt under the IRC wording, or the barrier manufacturer's instructions for other approved materials.
  4. Flash the openings shingle-fashion, integrated with the barrier as you go up rather than patched in afterwards.
  5. Plan the cutting before the material arrives. OSHA's construction standard for respirable crystalline silica, 29 CFR 1926.1153, has a line in its Table 1 for handheld power saws cutting fiber-cement board, blade diameter 8 inches or less. For work done outdoors only, it names a saw fitted with a commercially available dust collection system, with a collector giving at least the tool maker's recommended airflow and a filter of 99 percent or greater efficiency. A house with many openings and complicated gables means a great many of those cuts.
  6. Set the first course level off a starter strip and work up to the exposure, checking the course line against window heads as you go.

On cost, This Old House's fiber cement siding cost guide prices fiber cement at $5 to $14 per square foot installed, with labor alone at $2 to $8 and plank material at $0.70 to $6. Panels are priced separately at $2.50 to $15 for material. This site applies those rates to wall area rather than board area, so on the 1,500 sq ft wall in the table above our arithmetic gives $7,500 to $21,000 installed, and the same guide's exterior painting rate of $1 to $4 per square foot would add $1,500 to $6,000 if the board is primed rather than pre-finished. Last price check: 2026-09-08.

What this guide does not decide

It does not set clearances. Distance to grade, to a roof line, to a deck or to a horizontal surface are manufacturer figures, they vary by product, and this site has not read them, so it does not print them.

It does not handle the butt joints, the trim or the corners. Those are linear items driven by the shape of the building, and their detailing is in the installation instructions.

It does not know your wind speed or exposure category. Both come from your building department, and both decide whether the prescriptive path is open to you at all.

And dust from cutting is not a building code matter. It falls under OSHA's construction silica standard, which covers occupational exposure in construction work and sits outside IRC Chapter 7 entirely; Table 1 of that standard also tells the saw operator to follow the tool maker's instructions to minimize dust emissions.

Run the numbers

Frequently asked questions

How do you install fiber cement siding?
Confirm the wind exposure against Table R703.3.2 first, because four of its twelve cells have no prescriptive fastening answer. Then barrier over studs or sheathing on all exterior walls, with 2 in course laps and 6 in joint laps for felt under the IRC wording of R703.2, flashing shingle-fashion at every opening under R703.4, and courses laid to the exposure in the manufacturer's instructions, never with less than the 1 1/4 in lap R703.10.2 sets.
How much fiber cement siding do I need?
Take the net wall area and divide by the exposure to get linear feet. A 1,500 sq ft wall at a 7 in exposure needs 2,571 linear feet, and in an 8 1/4 in board that is 1,768 sq ft bought to cover 1,500 sq ft of wall. Add your waste allowance on top of that, not instead of it.
Can I choose the exposure on fiber cement?
Only within limits. R703.10.2 requires fiber cement lap siding to be lapped at least 1 1/4 in and installed in accordance with the manufacturer's instructions, so the exposure is the one printed for your product and can never leave a smaller lap. Settle it before anything else, because linear feet, courses and planks are all multiples of it.
What size nails does fiber cement siding need?
Not the figures in IRC R703.11. Those specify a 0.120 in shank with a 0.313 in head and 1 1/4 in penetration, and that section is titled vinyl siding. Table R703.3(1) has its own fiber cement rows, with 6d common nails, 2 in by 0.113 in, into studs through wood structural panel sheathing, and R703.10 points lap siding to the manufacturer's installation instructions.
How long does fiber cement siding last?
IRC Chapter 7 sets no service life. This Old House's cost guide lists a 50 year life with proper installation among its pros and says some companies offer a 30-year warranty, without saying what the 50 years rests on. What the code does govern is the barrier and flashing behind the cladding, and the maker's warranty is the document that states terms for your product.
What goes behind fiber cement siding?
A water-resistive barrier under R703.2. The IRC wording calls for one layer of No. 15 asphalt felt to ASTM D226 Type 1, or other approved barrier, free from holes and breaks, over studs or sheathing on all exterior walls, with felt lapped 2 in between courses and 6 in at joints. Other approved materials follow their manufacturer's instructions, and the Seattle code follows that wording with a replacement of its own.
When does fiber cement siding need engineered fastening?
Whenever the design wind pressure exceeds 30 psf, or the mean roof height exceeds the limit in Table R703.3.2 for your wind speed and exposure category. At 140 mph in Exposure C or D, 130 in D and 120 in D the table gives no permitted height at all, so the attachment must be designed for component and cladding loads.
Is cutting fiber cement dangerous?
OSHA treats it as a respirable crystalline silica task. Table 1 of 29 CFR 1926.1153 lists handheld power saws for cutting fiber-cement board, with blades of 8 inches or less, and for outdoor work only it specifies a saw with a commercially available dust collection system meeting the tool maker's airflow and a filter of 99 percent or greater efficiency.

Check these numbers yourself

Figures here last checked against the source documents on 2026-09-16. Codes are amended locally; confirm against the edition your jurisdiction enforces.

About the author

Lucas Pradella builds and maintains Nails & Numbers. He is not a tradesperson: every figure on the site is traced to a named, dated document, and the page links it so you can check it yourself. More about how these pages are made.

Every guide on this site: Guides.