Exhaust Fan CFM Calculator
2021 IRC M1505.4.3 and M1505.4.4
A bathroom fan needs 50 cfm if it runs when someone switches it on, or 20 cfm if it never stops. The room size does not enter into it. The whole house is a different number again, set by floor area and bedrooms.
Exhaust and ventilation airflow from the 2021 IRC
Minimum airflow at the fan. A long duct run delivers less than the fan's label.
Specification summary
Generated from on . Reopen that address to reproduce these figures exactly.
Entered
Result
Worked example
- Equation 15-1. 0.01 × 2,000 + 7.5 × (3 + 1) = 20 + 30 = 50 cfm continuous.
- Table M1505.4.3(1). 1,501 to 3,000 sq ft with 2 to 3 bedrooms reads 60 cfm. The code accepts either, so the equation's 50 is the minimum.
- Intermittent operation. At 50 percent run time Table M1505.4.3(2) gives a factor of 2, so the fan must move 100 cfm while it runs.
The formula
- Table M1505.4.4
- kitchens 100 cfm intermittent or 25 continuous; bathrooms and toilet rooms 50 intermittent or 20 continuous
- Equation 15-1
- the continuous whole-house rate, or Table M1505.4.3(1) instead
- Table M1505.4.3(2)
- run-time factor: 4 at 25%, 3 at 33%, 2 at 50%, 1.5 at 66%, 1.3 at 75%, interpolated between
- ACH
- air changes per hour, a target you choose; 60 turns hours into minutes
Where the numbers come from
Intermittent or continuous, and why the numbers are so far apart
Air changes per hour for any other room
Frequently asked questions
- What size bathroom exhaust fan do I need?
- 50 cfm if it runs intermittently, or 20 cfm if it runs continuously, under 2021 IRC Table M1505.4.4. The size of the bathroom does not change the minimum. Choose a fan labeled at or above that rate, because M1505.3 requires the airflow to be listed and labeled.
- How many cfm does a range hood need?
- The residential code's minimum for kitchen exhaust is 100 cfm intermittent or 25 cfm continuous. That is the floor for any kitchen, not a sizing rule for a particular range, and some jurisdictions amend it: Washington requires a minimum capture efficiency or 160 cfm for an electric range and 250 cfm for a combustion range.
- How do I calculate cfm for a room?
- Multiply length, width and ceiling height to get cubic feet, multiply by the air changes per hour you want, and divide by 60. A 12 by 10 ft room with an 8 ft ceiling at 6 air changes an hour needs 96 cfm.
- How much whole-house ventilation does a house need?
- 0.01 cfm per square foot plus 7.5 cfm per bedroom plus one, running continuously, by Equation 15-1. A 2,000 sq ft, three-bedroom house needs 50 cfm, or 60 cfm from Table M1505.4.3(1), and the code accepts either. A fan that runs half the time must move twice that.
- Can the bathroom fan be the whole-house ventilation?
- Yes. M1505.4.1 permits local exhaust fans to serve as the whole-house system, provided the fan meets the whole-house rate and has the manual override control M1505.4.2 requires.
Check these numbers yourself
- 2021 IRC Section M1505, Mechanical Ventilation, reprinted in Whole-House Mechanical Ventilation OptionsCity of Scottsdale, Arizona, rev. 3/10/23. Read 2026-09-15. Tables M1505.4.3(1), M1505.4.3(2) and M1505.4.4 and Equation 15-1; the amendment to M1505.2 is marked as Scottsdale's.
- WAC 51-51-1505, Section M1505 Mechanical ventilationWashington State Legislature, effective March 16, 2024. Read 2026-09-15. Source of the Washington kitchen amendment quoted in the FAQ.
How every figure here is verified: Sources & Method. Who builds this: About. Found something wrong? Tell us and it gets fixed or removed.
Figures on this page last checked against the source documents on 2026-09-15. Codes are amended locally; confirm against the edition your jurisdiction enforces.
Related calculators
- Duct Size Calculator the duct the fan pushes through
- Attic Ventilation Calculator attic vents, a different rule
- BTU Calculator heat loss by surface
- Heat Load Calculator the whole-house load
- AC Tonnage Calculator 12,000 Btu/h per ton by definition
- Furnace Size and Cost Calculator IRC M1401.3 against the 30 to 60 BTU per square foot rule
These are code minimums at the fan. A fan's label is measured at a stated static pressure, and duct length, elbows and the termination cap reduce what it delivers. Exhaust to the outdoors, never into an attic or crawl space (M1505.2).