Nails & Numbers

HomeHVAC › Heat Load Calculator: Heating Load by County

Heat Load Calculator: Heating Load by County

ENERGY STAR county design temperatures, IRC N1102.4.1.2 air leakage, conduction plus infiltration

A Manual J needs a design temperature, the envelope and the air a house leaks. ENERGY STAR publishes a heating and cooling design temperature for every one of 3,141 counties, the residential code caps air leakage at 5.0 air changes an hour at 50 pascals, and the heat air carries is a published constant. This page adds them up into a heating load, shows how much of it is air leakage, and names everything a real Manual J adds.

Heating load from your county, your envelope and your air leakage

ft
ft
ft
R
R
R
sq ft
U
sq ft
R
ACH50

Single storey box: floor area from length and width, walls from perimeter and height. Indoor 70°F heating and 75°F cooling, as the ENERGY STAR HVAC Design Report requires.

Specification summary

Generated from on . Reopen that address to reproduce these figures exactly.

Entered

Result

This bar is drawn from the house you enter above.
Where the design heating load goes

Worked example

A 50 by 40 ft single storey house in Cook County, Illinois, 9 ft walls, R-19 walls and R-38 ceiling (the DOE guide's Chicago house), 240 sq ft of U-0.30 windows, at the code's 5.0 ACH50.

  1. Design temperature. ENERGY STAR limit for Cook County: -3°F. 70 less -3 = 73°F.
  2. Conduction. UA 203.2 × 73 = 14,831 BTU/h.
  3. Air leakage. 5.0 ACH50 ÷ 20 = 0.25 ACH, 75 cfm in 18,000 cu ft; 1.08 × 75 × 73 = 5,913 BTU/h.
  4. Heating load. 14,831 + 5,913 = 20,744 BTU/h before duct losses.

Dividing by 26.5 instead, the DOE guide's ratio, takes the air leakage part to 4,463 BTU/h. The DOE guide's own Chicago house, a different and larger design with a conditioned basement, came to 41,700 BTU/h in Manual J.

The formula

Two terms, both at the heating temperature difference:

Q = (Σ U × A + 1.08 × cfm) × (70 − Tdesign)
U × A
each wall, ceiling, floor, window and door: area over R, or U from the window label
cfm
ACH50 ÷ 20 or 26.5 × volume ÷ 60
1.08
0.075 lb/cu ft × 0.240 Btu/lb·°F × 60 min, NREL BESTEST-EX air properties
Tdesign
ENERGY STAR 99% heating limit for the county

No solar or internal gains are credited on the heating side; the DOE guide notes the peak heat loss comes at night.

Why this is a heating load and not a Manual J

Manual J is published by ACCA and is not free to read, so this page does not claim to follow it.

What it does use is public: ENERGY STAR's county design temperatures and indoor conditions, the residential code's air leakage limit, NREL's air properties and the DOE Building America guide to load calculations. Each is named where it is used.

The design temperature for every county, and why it is a limit

ENERGY STAR publishes a heating and a cooling design temperature for every county in the country, for the load calculations its certified homes need. They come from the ASHRAE 2017 Fundamentals and Manual J 8th edition weather stations. They are limits, not averages: where several stations lie within 40 miles of a county's centre the guide takes the coldest heating figure among them, and it rounds in the cautious direction:

Cooling design temperatures were rounded up to the nearest integer (e.g., 90.2 °F rounded up to 91 °F), and heating design temperatures were rounded down to the nearest integer (e.g., 14.8 °F rounded down to 14 °F).

So the limit can be colder than the station a designer would pick. The Department of Energy's own worked example shows it:

Manual J design temperature in the DOE guide, June 2011, against the ENERGY STAR county limit
HouseDOE guide heating designENERGY STAR limitLimit against guide
Chicago House2°FCook County, Illinois: -3°F5°F colder
Orlando House42°FOrange County, Florida: 38°F4°F colder

The calculator uses the limit, because it is the only county-level list that is free to read. A load calculated from it is larger than one from the nearest station. For the Chicago house, five degrees on a 68 degree difference is about seven per cent.

ENERGY STAR design temperature limits, 2019 Edition, by state: 3,141 counties
StateCountiesColdest heating limitMildest heating limitHottest cooling limit
Alabama6716°F, Cullman30°F, Washington97°F, Russell
Alaska27-46°F, Southeast Fairbanks20°F, Prince of Wales-Hyder80°F, Yukon-Koyukuk
Arizona15-13°F, Apache27°F, Yuma116°F, Mohave
Arkansas7514°F, Fulton26°F, Miller100°F, Sevier
California58-13°F, Mono33°F, Imperial118°F, Inyo
Colorado64-14°F, Chaffee9°F, Mesa99°F, Prowers
Connecticut80°F, Hartford7°F, New London89°F, Windham
Delaware311°F, Kent18°F, Sussex91°F, Sussex
District of Columbia114°F, District of Columbia14°F, District of Columbia94°F, District of Columbia
Florida6727°F, Okaloosa48°F, Miami-Dade97°F, Jackson
Georgia15918°F, Catoosa32°F, Toombs97°F, Webster
Hawaii531°F, Hawaii62°F, Kauai90°F, Honolulu
Idaho44-11°F, Custer15°F, Lewis97°F, Owyhee
Illinois102-4°F, Carroll15°F, Pope95°F, Union
Indiana92-1°F, Carroll12°F, Posey94°F, Warrick
Iowa99-21°F, Lyon1°F, Page93°F, Wayne
Kansas1052°F, Atchison12°F, Wilson101°F, Barber
Kentucky1205°F, Boone18°F, Wayne95°F, McCracken
Louisiana6424°F, Lincoln35°F, Terrebonne98°F, Winn
Maine16-18°F, Oxford7°F, Washington87°F, Oxford
Maryland244°F, Garrett20°F, St. Mary's94°F, Queen Anne's
Massachusetts14-3°F, Berkshire12°F, Nantucket90°F, Worcester
Michigan83-14°F, Gogebic9°F, Ottawa90°F, Wayne
Minnesota87-21°F, Koochiching-6°F, Houston90°F, Rock
Mississippi8219°F, Bolivar29°F, Jackson97°F, DeSoto
Missouri1150°F, Gentry17°F, Pemiscot98°F, Newton
Montana56-18°F, Blaine7°F, Ravalli95°F, Rosebud
Nebraska93-8°F, Scotts Bluff5°F, Thayer99°F, Red Willow
Nevada17-16°F, Elko17°F, Clark116°F, Clark
New Hampshire10-18°F, Carroll0°F, Strafford90°F, Rockingham
New Jersey213°F, Sussex13°F, Ocean92°F, Union
New Mexico331°F, Catron25°F, Sierra101°F, Hidalgo
New York62-12°F, Clinton10°F, Richmond92°F, Westchester
North Carolina10012°F, Alleghany31°F, Hyde95°F, Wake
North Dakota53-20°F, Pembina-9°F, Bowman97°F, Grant
Ohio881°F, Ashland10°F, Lawrence92°F, Washington
Oklahoma779°F, Cimarron25°F, Choctaw104°F, Tillman
Oregon362°F, Umatilla35°F, Curry96°F, Wheeler
Pennsylvania672°F, Cameron11°F, Philadelphia91°F, York
Rhode Island52°F, Providence9°F, Newport88°F, Providence
South Carolina4618°F, Oconee30°F, Colleton97°F, Hampton
South Dakota66-21°F, Lake-1°F, Tripp97°F, Perkins
Tennessee9512°F, Cheatham22°F, Sequatchie97°F, Wilson
Texas25411°F, Hansford40°F, Starr104°F, Wilbarger
Utah29-4°F, Garfield12°F, Wayne109°F, Washington
Vermont14-18°F, Essex-4°F, Windsor87°F, Windham
Virginia1347°F, Alleghany23°F, Northampton95°F, York
Washington390°F, Asotin29°F, Skamania98°F, Franklin
West Virginia554°F, Barbour15°F, Roane93°F, Jefferson
Wisconsin72-16°F, Ashland0°F, Ozaukee91°F, Kenosha
Wyoming23-13°F, Lincoln1°F, Laramie95°F, Big Horn

Air leakage: a code limit, and a conversion with no physics behind it

A blower door measures leakage at 50 pascals, far more pressure than wind and stack effect put on a house. The 2021 residential code caps it, in Utah's adoption:

The maximum air leakage rate for any building or dwelling unit under any compliance path shall not exceed 5.0 air changes per hour or 0.28 cubic feet per minute (CFM) per square foot

The load calculation needs the everyday rate instead. The common shortcut divides by 20. Researchers at NIST and Lawrence Berkeley National Laboratory traced where that came from, early 1980s field studies, and concluded plainly:

It is shown that there is no physical basis for LIRs.

The DOE guide does not use 20. Its Chicago baseline pairs 5.04 ACH50 with 0.19 natural air changes in the heating season, a ratio of 26.5. On this page's example house in Cook County, dividing by 20 gives an infiltration load of 5,913 BTU/h; the DOE ratio gives 4,458. The calculator offers both, because nobody can say which is right for a house without modelling its height, shielding and climate.

The heat the air carries is not in doubt. NREL's BESTEST-EX states the air properties it uses: 0.075 lb per cubic foot and 0.240 Btu per lb per degree, which is 1.08 BTU/h for every cfm and every degree.

What one colder number does to the load

The DOE guide took its two Manual J houses and changed only the design conditions, the way it says designers do to build in a cushion: the outdoor temperature moved to the mean extreme, and the indoor setpoints were swapped to 75°F in winter and 70°F in summer.

DOE Building America guide, June 2011, Tables 4 to 7
HouseOutdoor heating designBaseline heating loadWith changed conditionsChange
Chicago House2°F to -11°F41,700 BTU/h52,700 BTU/h+26%
Orlando House42°F to 30°F23,600 BTU/h37,800 BTU/h+60%

Its conclusion on the weather data:

The ASHRAE tabulated temperature data is adequate for calculating peak heating and cooling loads, and should not be increased as an additional safety factor.

That is why this page does not add a margin. The ENERGY STAR limit already leans cold, and the result is labelled as a heating load before duct losses, not a furnace size.

How to use the number

Compare it with the heating output on a quote, not the input. A furnace's rating plate gives input BTU; output depends on its efficiency.

Use your blower door result if you have one. A new house's energy code test report gives ACH50. For an older house without one, the code's 5.0 is not a guess at your house; enter a higher figure and watch the air leakage share rise.

Ask for the Manual J report. It adds duct losses, ventilation and the room-by-room split that sizes the ducts.

The sources, and what a Manual J adds

Read 2026-09-13.

Design Temperature Limit Reference Guide (2019 Edition), ENERGY STAR Single-Family New Homes and Multifamily New Construction, US EPA, revised 4/27/2021. Exhibit 1, 1% cooling and 99% heating design temperature limits for every county, and the method used to assign them.

National HVAC Design Report, Version 3.1 / 3.2 / 3.3 (Rev. 14), ENERGY STAR Single-Family New Homes, US EPA, revised 01/15/2025. Item 3.2, indoor design temperatures of 70 F heating and 75 F cooling.

Strategy Guideline: Accurate Heating and Cooling Load Calculations, Arlan Burdick, IBACOS, for the US Department of Energy Building America program, NREL, June 2011. Baseline and manipulated design conditions for a Chicago and an Orlando house, the resulting loads, and the baseline infiltration rates.

The Origin and Application of Leakage-Infiltration Ratios, Benjamin Jones, Andrew Persily (NIST) and Max Sherman (LBNL). Where the divide-by-20 rule came from and why it should be used for quick estimates at best.

Building Energy Simulation Test for Existing Homes (BESTEST-EX), Phase 1, Judkoff, Polly, Bianchi and Neymark, NREL/TP-550-47427, August 2010. Air properties for infiltration conductance: specific heat 0.240 Btu/(lb F), density 0.075 lb/ft3 at sea level.

Utah Residential Code 2021, Chapter 11 Energy Efficiency, International Residential Code 2021 as adopted with amendments in Utah, read through UpCodes with the jurisdiction and edition stated on the page. Section N1102.4.1.2, the 5.0 ACH50 air leakage limit. Virginia's 2021 adoption also says five.

A Manual J calculation goes room by room and adds what this page leaves out: duct losses where ducts run outside the insulation, mechanical ventilation, heat lost through a slab edge or a basement wall, and on the cooling side solar gain by window orientation, internal gains and moisture. The residential code refers to it; ask for the report with any quote.

Frequently asked questions

What is a heat load calculation?
The heat a house loses on a design winter night: conduction through walls, ceiling, floor, windows and doors, plus the air that leaks in, each multiplied by the difference between indoors and the design outdoor temperature. ACCA Manual J is the residential method the code refers to.
What design temperature should I use for my county?
ENERGY STAR publishes a 99% heating and 1% cooling limit for every county, from ASHRAE and Manual J weather stations. It takes the coldest station within 40 miles and rounds down, so a designer may use a slightly milder figure from the nearest station, or your jurisdiction's own value.
How do you convert ACH50 to natural infiltration?
The common rule divides by 20. NIST and LBNL researchers traced it to early 1980s studies and found no physical basis for it. The DOE Building America guide's Chicago example pairs 5.04 ACH50 with 0.19 air changes, a ratio of 26.5. This page offers both.
How much heat does leaking air carry?
1.08 BTU per hour for every cfm and every degree of temperature difference: 0.075 lb per cubic foot times 0.240 Btu per lb per degree times 60 minutes, the air properties NREL's BESTEST-EX uses.
Is this a Manual J calculation?
No. It leaves out duct losses, mechanical ventilation, slab edge and basement wall losses, and on the cooling side solar gain, internal gains and moisture. It is a heating load built from public data, labelled as such.
Should I add a safety factor?
The DOE guide shows why not: moving only the design conditions on its Chicago house raised the heating load from 41,700 to 52,700 BTU/h, 26 per cent, and its Orlando house by 60 per cent. The county limit this page uses already leans cold.

Check these numbers yourself

How every figure here is verified: Sources & Method. Who builds this: About. Found something wrong? Tell us and it gets fixed or removed.

Figures on this page last checked against the source documents on 2026-09-13. Codes are amended locally; confirm against the edition your jurisdiction enforces.

Related calculators

This is not a Manual J load calculation. Design temperatures are ENERGY STAR limits, the air leakage limit is quoted from Utah's 2021 adoption of the residential code, read on 13 September 2026; your jurisdiction may publish its own values. Duct losses, ventilation and cooling gains other than conduction are not included.