Home › Electrical › Wire Size Calculator
Wire Size Calculator
IRC Chapter 37 ampacity tables, the NEC's Table 310.16 reproduced for dwellings
The NEC's ampacity table is behind a login, but the residential code reprints it as Table E3705.1, and its widest column is the one you cannot size a breaker from. 12 AWG copper is listed at 30 amps at 90°C and protected at 20. The same 2/0 copper that serves a 200 amp house legally is one size too small for a 200 amp subpanel feeder. This calculator applies every limit the code stacks on top of the table.
Conductor size for a branch circuit, feeder or service
Continuous means a load expected to run three hours or more. Count current-carrying conductors in the raceway or bundle; a neutral carrying only unbalanced current and equipment grounds do not count. Ambient is the hottest air the run passes through.
Specification summary
Generated from on . Reopen that address to reproduce these figures exactly.
Entered
Result
Worked example
- 16 A, noncontinuous. Breaker 20 A. Terminations 60°C. 12 AWG copper: 30 A at 90°C, limited to 20 A at the terminals and by the small conductor rule.
- 24 A continuous. 125% is 30 A, so a 30 A breaker and 10 AWG.
- 18 A in an attic at 100°F with 8 conductors. 12 AWG derates to 30 × 0.91 × 0.70 = 19.1 A, below the 20 A breaker, so 10 AWG (25.5 A).
- 200 A service to the whole house. 83% is 166 A: 2/0 copper at 175 A.
- 200 A feeder to a subpanel. 100%: 3/0 copper at 200 A.
The formula
- Table E3705.1
- allowable ampacity by size, material and temperature rating
- correction
- Table E3705.2, for ambient air other than 86°F
- adjustment
- Table E3705.3, 80% for 4 to 6 current-carrying conductors down to 35% for 41 or more
- termination rating
- 60°C for circuits of 100 A or less unless marked, 75°C above
- small conductor cap
- 14 AWG copper 15 A, 12 AWG 20 A, 10 AWG 30 A; aluminum 12 AWG 15 A, 10 AWG 25 A, 8 AWG 30 A
Why this page reads the residential code
| Copper size | Table E3705.1 at 90°C | At 75°C | At 60°C | Largest breaker, E3705.5.3 | What governs |
|---|---|---|---|---|---|
| 14 AWG | 25 A | 20 A | 15 A | 15 A | 60°C terminals and the cap agree |
| 12 AWG | 30 A | 25 A | 20 A | 20 A | 60°C terminals and the cap agree |
| 10 AWG | 40 A | 35 A | 30 A | 30 A | 60°C terminals and the cap agree |
Read 2026-09-13. IRC 2021 Tables E3705.1 and E3705.5.3 as adopted in Utah.
Download this table as CSV. Same cells as printed above, nothing added.
The ampacity table's widest column is the one you cannot size from
The same wire, 200 amps for the house and not for the subpanel
What the common circuits come out as
The sources, and why the residential code
Frequently asked questions
- What size wire for a 20 amp breaker?
- 12 AWG copper for an ordinary circuit. IRC Table E3705.5.3 limits 12 AWG copper to a 20 A overcurrent device and 14 AWG to 15 A. In a hot space or a bundle of more than three current-carrying conductors it may need to be 10 AWG.
- What size wire for 30 amps?
- 10 AWG copper, which Table E3705.5.3 allows to be protected at 30 A. In aluminum, 8 AWG, which is limited to 30 A.
- What size wire for a 200 amp service?
- 2/0 copper or 4/0 aluminum for a service or feeder carrying the entire load of a one-family dwelling, from IRC Table E3603.1.1, which sizes those conductors at 83 per cent of the rating. A 200 A feeder to a subpanel serving part of the house needs 3/0 copper or 250 kcmil aluminum.
- What size wire for a 100 amp subpanel?
- At 100 A, 60°C terminations apply unless the equipment is marked 75°C. Copper needs 1 AWG at 60°C (110 A), or 3 AWG where the terminations are marked 75°C (100 A). Aluminum needs 1/0 at 60°C.
- Why is 12 gauge rated 30 amps in some charts?
- That is the 90°C column of the ampacity table. The IRC allows it only as the starting point for temperature and bundling adjustments; the breaker is limited to 20 A by the small conductor rule and the terminations are usually rated 60°C.
- How many wires can be in a conduit before derating?
- Three current-carrying conductors. From 4 to 6 the ampacity is 80 per cent of the table, 7 to 9 is 70 per cent, 10 to 20 is 50 per cent, per IRC Table E3705.3.
- Does wire size depend on distance?
- Not for ampacity. The code's ampacity tables have no length. A long run may need a larger wire for voltage drop, which the voltage drop calculator works out.
- Is this the NEC?
- It is the International Residential Code's electrical chapters, which reproduce the NEC's rules for one and two family dwellings with the NEC section cited in brackets. Where your jurisdiction adopts the NEC directly, confirm against its edition.
Check these numbers yourself
- Utah Residential Code 2021, Chapter 37IRC 2021 as adopted in Utah, read 2026-09-13 through UpCodes with the jurisdiction and edition stated on the page. Sections E3701.2 and E3705, Tables E3705.1, E3705.2, E3705.3, E3705.5.3 and E3705.6.
- Utah Residential Code 2021, Chapter 36IRC 2021 as adopted in Utah, read 2026-09-13. Section E3603.1.1 and Table E3603.1.1.
- Virginia Residential Code 2021, Chapter 37Read 2026-09-13 to confirm the Utah tables match another state's adoption character for character.
How every figure here is verified: Sources & Method. Who builds this: About. Found something wrong? Tell us and it gets fixed or removed.
Figures on this page last checked against the source documents on 2026-09-13. Codes are amended locally; confirm against the edition your jurisdiction enforces.
Related calculators
- Voltage Drop Calculator whether a long run needs a size larger
- Electricity Cost Calculator what the load costs to run
- Water Heater Size Calculator a common continuous load
- BTU Calculator the heating and cooling loads on the panel
- Conduit and Box Fill Calculator IRC Tables E3904.6(1) to (10) and E3905.12
- Electrical Work Cost Estimator HomeAdvisor's electrician and outlet guides
- Residential Electrical Load Calculator IRC Table E3602.2 for the service
- Solar Panel Calculator EIA estimated small-scale solar generation and capacity
Sizes follow the 2021 International Residential Code as adopted in Utah, read on 13 September 2026, which reproduces NEC rules for one and two family dwellings. Your jurisdiction may adopt the NEC directly, a different edition or amendments, and cable types can carry their own limits that this page does not apply. Electrical work is commonly permit work that must be done by a licensed electrician where required. This page does not size for voltage drop, grounding conductors or motor circuits.