Conduit Fill Chart
IRC Tables E3904.6(1) to (10), the residential reprint of NEC Annex C
NEC Annex C's conduit fill tables are reprinted in the residential code as Tables E3904.6(1) to (10), one per raceway. The charts below are the three raceways most houses use, EMT and PVC Schedule 40 and 80, for THHN. The lookup covers all ten raceways and three wire types, and finds the smallest conduit for the number of wires you are pulling.
Find the conduit
All conductors the same type and size, as the tables assume.
Specification summary
Generated from on . Reopen that address to reproduce these figures exactly.
Entered
Result
Worked example
- Table E3904.6(1), EMT. 12 AWG THHN: 9 in 1/2 in, 16 in 3/4 in.
- Smallest. 1/2 in EMT holds four with room to spare.
The formula
- raceway
- each of the ten types has its own table, because wall thickness changes the bore
- count
- the most conductors of one type and size the table allows
Where the numbers come from
EMT
PVC Schedule 40
PVC Schedule 80
Frequently asked questions
- How many 12 gauge wires fit in 1/2 inch EMT?
- Nine 12 AWG THHN in 1/2 in EMT and 16 in 3/4 in, from IRC Table E3904.6(1). In 1/2 in PVC Schedule 40 it is 8, and in Schedule 80 it is 6.
- How many 10 gauge wires fit in 3/4 inch conduit?
- Ten 10 AWG THHN in 3/4 in EMT, 9 in PVC Schedule 40 and 7 in PVC Schedule 80.
- Do I need to work out the fill percentage?
- Not for wires all of one type and size: Tables E3904.6 give the count directly. The percentage rule behind them, and the conductor areas for mixed fills, are in the NEC, which the residential code does not reprint.
- Is THHN the same as THWN for conduit fill?
- Yes in these tables: IRC Tables E3904.6 give THHN, THWN and THWN-2 one shared row, so the counts are the same.
- Where is the conduit fill table in the NEC?
- Annex C of the NEC. The residential code reprints it for dwellings as Tables E3904.6(1) through (10), one per raceway type.
Check these numbers yourself
- Utah Residential Code 2021, Chapter 39 Power and Lighting DistributionIRC 2021 as adopted in Utah, read through UpCodes. Tables E3904.6(1) to (10). Read 2026-09-13; Virginia's adoption prints all ten identically.
How every figure here is verified: Sources & Method. Who builds this: Lucas Pradella, and the method is on About. Found something wrong? Tell us and it gets fixed or removed.
Figures on this page last checked against the source documents on 2026-09-30. Codes are amended locally; confirm against the edition your jurisdiction enforces.
Related calculators
- Conduit Fill Calculator mixed wires and boxes
- Wire Ampacity Chart the amps per wire
- Wire Size Calculator the wire for a circuit
- Pipe and Conduit Offset Calculator bending the run
- Electrical Work Cost Estimator HomeAdvisor's electrician and outlet guides
- Recessed Lighting Cost Calculator HomeAdvisor's recessed and under-cabinet lighting guides
- Residential Electrical Load Calculator IRC Table E3602.2 for the service
- Solar Panel Calculator EIA estimated small-scale solar generation and capacity
- Transformer Sizing Calculator DOE 10 CFR 431.196 ratings and minimum efficiency
Dwelling tables from the residential code. Mixed conductor sizes, compact conductors and cable in raceway follow the NEC's conductor area tables.