Home › Electrical › Transformer Sizing Calculator
Transformer Sizing Calculator
DOE 10 CFR 431.196 ratings and minimum efficiency
A transformer is sized in kVA: volts times amps, times 1.732 on three phase, divided by 1,000. The size you can buy comes from a short list, and the federal efficiency standard is the one public place that list is printed with a number attached to every rating.
Low-voltage dry-type distribution transformer, sized from the load
Ratings and efficiencies are the DOE table for low-voltage dry-type units made from 2016 until April 23, 2029.
Specification summary
Generated from on . Reopen that address to reproduce these figures exactly.
Entered
Result
Worked example
- Load. 208 × 80 × 1.732 / 1,000 = 28.82 kVA, or 36.03 kVA with the 25% allowance.
- Rating. The DOE three-phase list runs 15, 30, 45, 75 kVA. 30 is too small, so 45 kVA, loaded to 80.1%.
- Currents. 45,000 / (208 × 1.732) = 124.9 A on the secondary and 54.1 A on the 480 V primary.
- Efficiency. The standard requires at least 98.40% at 35% load, which allows no more than 256 W of loss at that load.
- Fault current. 124.9 × 100 / 4.5 = 2,776 A available at the secondary terminals.
The formula
- √3
- 1.732, used on three phase only; single phase drops it
- kVA from kW
- kW divided by power factor
- %Z
- the impedance printed on the nameplate, in percent
- loss
- 35% of the rating in watts × (1 / efficiency − 1), the most the DOE minimum allows at the test load
Where the list of sizes comes from
Why the growth allowance decides the size
Primary current and the turns ratio
Frequently asked questions
- How do I calculate what size transformer I need?
- Multiply the load voltage by the load current, and by 1.732 on three phase, then divide by 1,000 for kVA. Add any allowance for growth and take the next standard rating up. An 80 A load at 208 V three phase is 28.82 kVA; with 25% added it needs a 45 kVA transformer.
- How many amps is a 75 kVA transformer?
- On three phase, 75,000 divided by (208 × 1.732) is 208.2 A at 208 V, and 75,000 divided by (480 × 1.732) is 90.2 A at 480 V. On single phase at 240 V it is 312.5 A.
- How do you calculate transformer fault current?
- Divide the secondary full-load current by the nameplate impedance as a decimal, or multiply it by 100 and divide by the percent impedance. A 45 kVA, 208 V three-phase unit carries 124.9 A at full load, so at 4.5% impedance it can deliver about 2,776 A into a fault at its terminals, assuming an unlimited supply.
- How do you convert kW to kVA?
- Divide kW by the power factor. 60 kW at a power factor of 0.85 is 70.6 kVA, which needs a 75 kVA three-phase transformer.
- What is the turns ratio of a transformer?
- The ratio of its primary to secondary voltage. 480 to 208 V is 2.31 to 1, and 480 to 240 V is 2 to 1. Current goes the other way, so the secondary carries that many times more amps than the primary.
Check these numbers yourself
- 10 CFR 431.196, Energy conservation standards and their effective datesUS Department of Energy, Electronic Code of Federal Regulations. Read 2026-09-15. Paragraph (a)(2): kVA ratings and minimum efficiencies at 35 percent load for low-voltage dry-type distribution transformers made from January 1, 2016 until April 23, 2029.
- How do you calculate the maximum possible Available Fault Current at the secondary for single-phase and three-phase Transformers?Schneider Electric FAQ FA105006, published 7/29/2003, last modified 6/22/2026. Read 2026-09-15. Secondary full-load current divided by impedance, assuming an infinite source.
How every figure here is verified: Sources & Method. Who builds this: About. Found something wrong? Tell us and it gets fixed or removed.
Figures on this page last checked against the source documents on 2026-09-15. Codes are amended locally; confirm against the edition your jurisdiction enforces.
Related calculators
- Electrical Load Calculator the load a service carries
- Wire Size Calculator conductors for the secondary
- Voltage Drop Calculator the run from the transformer
- Solar Panel Calculator another source of power
- Conduit and Box Fill Calculator IRC Tables E3904.6(1) to (10) and E3905.12
- Electrical Work Cost Estimator HomeAdvisor's electrician and outlet guides
- Watt and Electricity Cost Calculator Conversions from NIST SP 811
Sizing a transformer is part of an electrical design. Overcurrent protection, conductor sizing and grounding for the transformer are set by NEC Article 450 and your inspector, and none of them are on this page. The fault current is the transformer's maximum; the actual figure is lower once utility and conductor impedance are counted.