Nails & Numbers

Home › Electrical › Wire Ampacity Chart

Wire Ampacity Chart

IRC Table E3705.1, the residential reprint of NEC Table 310.16

The ampacity chart everybody looks up is NEC Table 310.16, which sits behind NFPA's login. The residential code prints the same values for dwellings as Table E3705.1, with the NEC section in brackets, and that is the chart below: every size from 14 AWG to 900 kcmil, copper and aluminum, at 60, 75 and 90°C. Pick a size and the calculator reads the row, applies the ambient and bundling factors, and gives the breaker limit the table leaves out.

Look up a wire

no.

Enter how many conductors in the raceway or cable carry current; Table E3705.3 sets the factor.

Specification summary

Generated from on . Reopen that address to reproduce these figures exactly.

Entered

Result

Worked example

12 AWG THHN copper, three conductors, at a normal room temperature.

  1. Table E3705.1. 12 AWG copper reads 20 A at 60°C, 25 A at 75°C and 30 A at 90°C.
  2. Breaker limit. E3705.5.3 caps 12 AWG copper at 20 A whatever the column says.

The 30 A in the 90°C column is real, and it is for derating from, not for sizing the breaker.

The formula

Read the row, then apply the two factors the code prints beside it:

adjusted ampacity = Table E3705.1 value × ambient factor (E3705.2) × bundling factor (E3705.3)
ambient factor
1.00 at 78 to 86°F, lower in a hot attic
bundling factor
80% for 4 to 6 current-carrying conductors, 70% for 7 to 9, 50% for 10 to 20

Then the breaker is limited by E3705.5.3 for 14, 12 and 10 AWG copper and 12, 10 and 8 AWG aluminum.

Where the numbers come from

The chart is IRC 2021 Table E3705.1, read from the Utah Residential Code and confirmed identical in Virginia's adoption. It carries NEC Table 310.16's values for the conductors used in dwellings, and the correction and adjustment tables are E3705.2 and E3705.3.

Every cell was checked to rise with wire size and with the temperature column. None fails.

The chart: ampacity by wire size

IRC Table E3705.1 (NEC 310.16 values), amperes, not more than three current-carrying conductors, 86°F ambient
SizeCopper 60°CCopper 75°CCopper 90°CAluminum 60°CAluminum 75°CAluminum 90°C
14 AWG152025---
12 AWG202530152025
10 AWG303540253035
8 AWG405055354045
6 AWG556575405055
4 AWG708595556575
3 AWG85100115657585
2 AWG951151307590100
1 AWG11013014585100115
1/0 AWG125150170100120135
2/0 AWG145175195115135150
3/0 AWG165200225130155175
4/0 AWG195230260150180205
250 kcmil215255290170205230
300 kcmil240285320195230260
350 kcmil260310350210250280
400 kcmil280335380225270305
500 kcmil320380430260310350
600 kcmil350420475285340385
700 kcmil385460520315375425
750 kcmil400475535320385435
800 kcmil410490555330395445
900 kcmil435520585355425480

A dash means the table lists no ampacity: aluminum starts at 12 AWG.

What size wire for each breaker

The chart answers "how many amps can this wire carry". The question most people start from is the reverse. Reading it backwards, with the small-conductor limits applied:

Smallest wire from Table E3705.1 with E3705.5.3 applied, normal ambient, three or fewer conductors
BreakerCopper at 60°CCopper at 75°CAluminum at 75°C
15 A14 AWG14 AWG12 AWG
20 A12 AWG12 AWG10 AWG
30 A10 AWG10 AWG8 AWG
40 A8 AWG8 AWG6 AWG
50 A6 AWG8 AWG6 AWG
60 A4 AWG6 AWG4 AWG
70 A4 AWG4 AWG3 AWG
100 A1 AWG3 AWG1 AWG
125 A1/0 AWG1 AWG2/0 AWG
150 A3/0 AWG1/0 AWG3/0 AWG
200 A250 kcmil3/0 AWG250 kcmil

The 60°C column is the one for ordinary household circuits of 100 A or less, because that is the rating the code assumes for their terminals. A 20 A aluminum circuit needs 10 AWG, not 12: the table gives 12 AWG aluminum 20 A at 75°C, but E3705.5.3 caps it at 15 A.

Why three columns, and which one to read

The three columns are the insulation's temperature rating, not three grades of copper. A wire can carry more current if its insulation tolerates more heat, so the 90°C column is always the largest.

The code lets you start from the 90°C figure when you derate for a hot space or a full raceway, and then requires the result to be no more than the terminal column allows. That is why 12 AWG THHN shows 30 A and is still a 20 A wire in a house.

Frequently asked questions

How many amps can 12 gauge wire carry?
12 AWG copper is 20 A at 60°C, 25 A at 75°C and 30 A at 90°C in Table E3705.1, but E3705.5.3 limits its breaker to 20 A. For a household circuit, 12 AWG copper is a 20 A wire.
How many amps can 10 gauge wire carry?
10 AWG copper is 30, 35 and 40 A in the three columns, and E3705.5.3 caps its breaker at 30 A. 10 AWG aluminum is 25, 30 and 35 A, capped at 25 A.
What size wire for 50 amps?
8 AWG copper at 75°C (50 A) where the terminals are rated 75°C, or 6 AWG copper at 60°C (55 A). In aluminum, 6 AWG at 75°C (50 A).
What size wire for 100 amps?
3 AWG copper at 75°C (100 A) or 1 AWG aluminum at 75°C (100 A) as a branch or feeder. A dwelling service or main feeder can use a smaller size under Table E3603.1.1, which the wire size calculator explains.
Is Table E3705.1 the same as NEC 310.16?
It carries NEC Table 310.16's values, reprinted in the residential code for one and two family dwellings with the NEC section cited in brackets. It is the free, public version of the same numbers.
How do I derate wire for more conductors?
Multiply the table value by 80% for 4 to 6 current-carrying conductors, 70% for 7 to 9, 50% for 10 to 20, 45% for 21 to 30, 40% for 31 to 40 and 35% above that, from Table E3705.3.

Check these numbers yourself

How every figure here is verified: Sources & Method. Who builds this: , and the method is on About. Found something wrong? Tell us and it gets fixed or removed.

Figures on this page last checked against the source documents on 2026-09-30. Codes are amended locally; confirm against the edition your jurisdiction enforces.

Related calculators

Dwelling values from the residential code. Commercial work, other conductor types and conditions outside these tables follow the NEC itself and your inspector.