Home › Electrical › Wire Ampacity Chart
Wire Ampacity Chart
IRC Table E3705.1, the residential reprint of NEC Table 310.16
The ampacity chart everybody looks up is NEC Table 310.16, which sits behind NFPA's login. The residential code prints the same values for dwellings as Table E3705.1, with the NEC section in brackets, and that is the chart below: every size from 14 AWG to 900 kcmil, copper and aluminum, at 60, 75 and 90°C. Pick a size and the calculator reads the row, applies the ambient and bundling factors, and gives the breaker limit the table leaves out.
Look up a wire
Enter how many conductors in the raceway or cable carry current; Table E3705.3 sets the factor.
Specification summary
Generated from on . Reopen that address to reproduce these figures exactly.
Entered
Result
Worked example
- Table E3705.1. 12 AWG copper reads 20 A at 60°C, 25 A at 75°C and 30 A at 90°C.
- Breaker limit. E3705.5.3 caps 12 AWG copper at 20 A whatever the column says.
The formula
- ambient factor
- 1.00 at 78 to 86°F, lower in a hot attic
- bundling factor
- 80% for 4 to 6 current-carrying conductors, 70% for 7 to 9, 50% for 10 to 20
Where the numbers come from
The chart: ampacity by wire size
What size wire for each breaker
Why three columns, and which one to read
Frequently asked questions
- How many amps can 12 gauge wire carry?
- 12 AWG copper is 20 A at 60°C, 25 A at 75°C and 30 A at 90°C in Table E3705.1, but E3705.5.3 limits its breaker to 20 A. For a household circuit, 12 AWG copper is a 20 A wire.
- How many amps can 10 gauge wire carry?
- 10 AWG copper is 30, 35 and 40 A in the three columns, and E3705.5.3 caps its breaker at 30 A. 10 AWG aluminum is 25, 30 and 35 A, capped at 25 A.
- What size wire for 50 amps?
- 8 AWG copper at 75°C (50 A) where the terminals are rated 75°C, or 6 AWG copper at 60°C (55 A). In aluminum, 6 AWG at 75°C (50 A).
- What size wire for 100 amps?
- 3 AWG copper at 75°C (100 A) or 1 AWG aluminum at 75°C (100 A) as a branch or feeder. A dwelling service or main feeder can use a smaller size under Table E3603.1.1, which the wire size calculator explains.
- Is Table E3705.1 the same as NEC 310.16?
- It carries NEC Table 310.16's values, reprinted in the residential code for one and two family dwellings with the NEC section cited in brackets. It is the free, public version of the same numbers.
- How do I derate wire for more conductors?
- Multiply the table value by 80% for 4 to 6 current-carrying conductors, 70% for 7 to 9, 50% for 10 to 20, 45% for 21 to 30, 40% for 31 to 40 and 35% above that, from Table E3705.3.
Check these numbers yourself
- Utah Residential Code 2021, Chapter 37 Branch Circuit and Feeder RequirementsIRC 2021 as adopted in Utah, read through UpCodes. Tables E3705.1, E3705.2, E3705.3 and Section E3705.5.3, with the NEC sections in brackets. Read 2026-09-13; Virginia's adoption prints the same tables identically.
How every figure here is verified: Sources & Method. Who builds this: Lucas Pradella, and the method is on About. Found something wrong? Tell us and it gets fixed or removed.
Figures on this page last checked against the source documents on 2026-09-30. Codes are amended locally; confirm against the edition your jurisdiction enforces.
Related calculators
- Wire Size Calculator the wire for a circuit
- Voltage Drop Calculator long runs
- Conduit Fill Chart how many of them fit
- Panel Load Calculator the service size
- Conduit and Box Fill Calculator IRC Tables E3904.6(1) to (10) and E3905.12
- Electrical Work Cost Estimator HomeAdvisor's electrician and outlet guides
- Recessed Lighting Cost Calculator HomeAdvisor's recessed and under-cabinet lighting guides
- Solar Panel Calculator EIA estimated small-scale solar generation and capacity
- Transformer Sizing Calculator DOE 10 CFR 431.196 ratings and minimum efficiency
Dwelling values from the residential code. Commercial work, other conductor types and conditions outside these tables follow the NEC itself and your inspector.